  "title": "Scaling a 4–20 mA Loop Without the Offset Mistakes",
  "url": "https://urgent.news/2026/11/25/scaling-a-4-20-ma-loop-without-the-offset-mistakes",
  "topic": "tech",
  "section": "Tech",
  "published": "2026-11-25T17:35:24.000Z",
  "source": {
    "name": "Dev.to",
    "slug": "dev-to",
    "url": "https://dev.to/gridcircuits/scaling-a-4-20-ma-loop-without-the-offset-mistakes-33om"
  },
  "original_language": "en",
  "account": "A 4-20 mA current loop remains a popular method for transmitting measurements from field transmitters to PLCs, RTUs, or SCADA systems. Scaling mistakes are subtle and often go unnoticed because the readings still appear plausible.\n\nFirst and foremost, understand that 4 mA represents the live zero, not a zero reading. A 0 mA reading indicates a broken wire, dead transmitter, or lost power supply. This distinction is crucial before any scaling takes place.\n\nThe scaling formula for a transmitter with an LRV (lower range value) and an URV (upper range value) is: Engineering value = LRV + (mA - 4) / 16 × (URV - LRV). The 16 in the denominator represents the loop's span (20 mA - 4 mA). Every milliamp above the live zero equals one-sixteenth of the engineering span.\n\nFor example, consider a 0-150 psi pressure transmitter and 12 mA. The calculation would be: 0 + (12 - 4) / 16 × 150 = 75 psi. This represents half the loop span and engineering span, as expected.\n\nTwo common scaling errors exist. The first is treating the signal as 0-20 mA instead of a 16 mA span. Scaling 12 mA as a fraction of 20 mA leads to an incorrect value of 90 psi, which is 20% of the span. The error is noticeable at the live zero and worst when the reading is near zero. The second mistake occurs when scaling raw counts without removing the 4 mA offset. This results in every reading being shifted upward by the same amount, corrupting trend data and control decisions.\n\nTo scale values in reverse, use the formula: mA = 4 + (EU - LRV) / (URV - LRV) × 16. Verify the three critical points - 4 mA for LRV, 20 mA for URV, and 0 mA as a fault - before trusting any scaled values. Always confirm these points to ensure the accuracy of the entire loop.",
  "summary": "A 4–20 mA current loop is still one of the most common ways to move a measurement from a field transmitter into a PLC, RTU, or SCADA system — and one of the easiest to scale incorrectly. The math itself is simple. The mistakes are subtle, and they hide in plain sight because the readings still look plausible. What 4–20 mA really means A 4–20 mA loop carries a measurement as a fraction of span: 4…",
  "key_points": [
    "4 mA signifies live zero, not zero reading",
    "Scaling formula: Engineering value = LRV + (mA - 4) / 16 × (URV - LRV)",
    "Common errors: treating signal as 0-20 mA, scaling raw counts without offset"
  ],