  "title": "Fire Alarm Standby Battery Sizing: The Calculation I Run Before Specifying a Panel Battery",
  "url": "https://urgent.news/2026/11/20/fire-alarm-standby-battery-sizing-the-calculation-i-run-before",
  "topic": "tech",
  "section": "Tech",
  "published": "2026-11-20T14:06:41.000Z",
  "source": {
    "name": "Dev.to",
    "slug": "dev-to",
    "url": "https://dev.to/chenyuelv/fire-alarm-standby-battery-sizing-the-calculation-i-run-before-specifying-a-panel-battery-1d1g"
  },
  "original_language": "en",
  "account": "Fire-alarm standby battery sizing requires a methodical approach beyond just picking a block from a panel brochure. The battery specification hinges on the device list, panel current, adopted standby and alarm durations by the authority having jurisdiction, and a derating factor for battery aging. Experienced ELV and fire-alarm designer Chen Yu notes common errors, such as leaving out sounder alarm currents, treating the panel as if it draws no power, arbitrarily choosing a block size, and not accounting for battery end-of-life capacity.\n\nEvery device and the panel itself have standby and alarm currents. Standby current is what the system draws after a mains failure while in normal monitoring state, with detectors, panel CPU, display, loops, and normally-energized loads like electromagnetic door holders. Alarm current is the system draw during an alarm, covering sounders, beacons, voice-alarm amplifiers, detector alarm LEDs, and alarm relays. Not all loads remain active during alarm; some, like door holders, draw current only in standby. Both standby and alarm currents contribute to the required amp-hour capacity, calculated using the formula: Ah_required = (I_standby * T_standby + I_alarm * T_alarm) * F. I_standby and I_alarm are the system totals in amperes, T_standby and T_alarm are the standby and alarm times in hours, and F is a derating factor, typically 1.25 to cover battery aging.\n\nStandby and alarm times are specified in national installation codes, such as 24 hours of standby and 30 minutes in alarm. Other codes might prescribe different durations, like 8 hours standby and 30 minutes alarm in China. The amp-hour calculation involves multiplying standby and alarm currents by their respective durations, summing the results, and multiplying by the derating factor. For example, on a 24 V addressable panel with 24 hours standby, 30 minutes alarm, and a derating factor of 1.25, a small office building requiring 40 addressable smoke detectors, heat detectors, manual call points, sounder-beacons, a loop isolator, and a door holder calculated to have 641.1 mA standby and 955.6 mA alarm results in a required battery capacity of 19.83 Ah. Using next standard VRLA battery sizes, a 26 Ah battery would be appropriate.",
  "summary": "By Chen Yu, ELV (extra-low-voltage) systems designer since 1998 I do not pick a fire-alarm battery from the panel brochure. The brochure tells me which block sizes the cabinet will accept. The size I need comes from the device list, the panel's own current, the standby and alarm durations the authority having jurisdiction has adopted, and a factor for a battery that is no longer new. Over 25+…",
  "key_points": [],
  "editors_take": null,
  "illustration": null,
  "coverage": {
    "outlets": 1,
    "also_reported_by": []
  },
  "ai_generated": true,
  "disclaimer": "Summaries, key points and the editor’s take are written by software from other outlets’ reporting and may contain errors — always check the linked original."
}